Data record std.astm-d6871.structure.appendix-x2.mineral-oil-comparison
Verified 2026-10-24 Confidence: Medium
Appendix X2 of ASTM D6871-26 contrasts a natural ester with a mineral oil: the interfacial tension of new ester typically reads lower, the dissipation factor and the neutralization number typically read higher, and the water saturation level of an ester is far above that of a mineral oil, so water content in an ester is better judged as a fraction of saturation than as an absolute concentration.
| Step | Item | Detail |
|---|---|---|
| Source | ASTM D6871-26 | Licensed standard, clause X2.1.2, X2.2.1, X2.3.1, X2.3.2 |
| Data record | std.astm-d6871.structure.appendix-x2.mineral-oil-comparison | Verified 2026-10-24 |
| Entry | Standard Specification for Natural (Vegetable Oil) Ester Fluids Used in Electrical Apparatus | No revisions |
- Subject
- Standard Specification for Natural (Vegetable Oil) Ester Fluids Used in Electrical Apparatus (Standards)
- Kind
- Standard scope
- Source
- ASTM D6871-26, clause X2.1.2, X2.2.1, X2.3.1, X2.3.2, Natural (Vegetable Oil) Ester Fluids Used in Electrical Apparatus, ASTM International. Publisher page
History
| Date | Change |
|---|---|
| 2026-10-24 | created |
| 2026-10-24 | review_status unreviewed -> software_reviewed |
| 2026-10-27 | hold lifted |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record std.astm-d6871.structure.appendix-x2.mineral-oil-comparison." Insulating Fluid Reference. 2026-10-27. https://www.insulatingfluidreference.com/data/std.astm-d6871.structure.appendix-x2.mineral-oil-comparison/.
Insulating Fluid Reference, Data record std.astm-d6871.structure.appendix-x2.mineral-oil-comparison (Oct. 27, 2026), https://www.insulatingfluidreference.com/data/std.astm-d6871.structure.appendix-x2.mineral-oil-comparison/.
@misc{etr-data-std-astm-d6871-structure-appendix-x2-mineral-oil-comparison,
title = {Data record std.astm-d6871.structure.appendix-x2.mineral-oil-comparison},
howpublished = {\url{https://www.insulatingfluidreference.com/data/std.astm-d6871.structure.appendix-x2.mineral-oil-comparison/}},
organization = {Insulating Fluid Reference},
publisher = {Insulating Fluid Reference},
year = {2026},
note = {last substantive change 2026-10-27}
}{{cite web |title=Data record std.astm-d6871.structure.appendix-x2.mineral-oil-comparison |website=Insulating Fluid Reference |publisher=Insulating Fluid Reference |url=https://www.insulatingfluidreference.com/data/std.astm-d6871.structure.appendix-x2.mineral-oil-comparison/ |date=2026-10-27 |access-date=}}